CVE-2022-33174
high-risk
Published 2022-06-13
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Do I need to act?
!
72.0% chance of exploitation in next 30 days
EPSS score — higher than 28% of all CVEs
-
Not on CISA KEV list
No confirmed active exploitation reported to CISA
?
Patch status unknown
Check vendor advisories for fix availability and mitigation guidance